ZERORISKK · SLD STUDIO LEARNING COURSE

Build it. Check it. Explain the result.

Use this worksheet beside the 56-minute silent video. Draw one complete branch with the lesson, then pause to build the repeated branches using the schedules below. Finally run the studies and explain the findings in your own words.

Download the completed practice SLD · Download the caption transcript

These are provisional teaching inputs and relay settings. Some example duties fail or remain indeterminate. Reproducing a result demonstrates software use; it does not approve the electrical design or authorize relay settings for service.

1. Draw and organize your circuit

  1. Start a new SLD. Set a meaningful drawing title, project, revision and 50 Hz system frequency. Create 132 kV, 33 kV and 11 kV voltage levels. Keep grid snap on.
  2. Place three 33 kV buses in one horizontal row. Name them Bus A, Bus B and Bus C. Give each bus a 900 px drawing length and 2000 A continuous-current rating.
  3. Place Bus Coupler 1 between Bus A and Bus B, and Bus Coupler 2 between Bus B and Bus C. Rotate each coupler horizontally and connect its terminals to the facing bus ends.
  4. Build the two grid incomers, six generator branches and three motor feeders listed below. Follow the video to place, rotate, name, connect and parameterize one example of each equipment type.
  5. Duplicate complete branches to save time. Review every copied name, voltage, rating and service state. Copying a branch preserves its electrical data; it does not make those values correct for a different feeder.
  6. Align equipment centres before straightening wires. Use vertical feeder paths and horizontal bus-coupler paths. Automatic wire routing removes unnecessary manual bends. Reserve space for bus taps, labels and relay links.
  7. Place the 15 relays. Assign each relay's measured breaker terminal, CT ratio, stage settings and trip breaker. Electrical conductors, relay measurement associations and relay trip links serve different purposes.
  8. Save your editable project. Compare it with the completed practice file: 52 equipment, 51 explicit connections, 15 relays, two open breakers. Dashed measurement associations can need an elbow to reach a different measurement terminal; the explicit power and trip connections in this practice drawing are straight.

Branch plan

BranchConnect in this order
Grid incomer 1Grid 1 → Overhead Line 1 → Breaker 1 → Transformer 1 → Breaker 2 → Bus A
Grid incomer 2Grid 2 → Overhead Line 2 → Breaker 3 → Transformer 2 → Breaker 4 → Bus C
Generator branch 1Generator 1 → Transformer 3 → Breaker 5 → Bus A
Generator branch 2Generator 2 → Transformer 4 → Breaker 6 → Bus A
Generator branch 3Generator 3 → Transformer 5 → Breaker 7 → Bus B
Generator branch 4Generator 4 → Transformer 6 → Breaker 8 → Bus B
Generator branch 5Generator 5 → Transformer 7 → Breaker 9 → Bus C
Generator branch 6Generator 6 → Transformer 8 → Breaker 10 → Bus C
Motor feeder ABus A → Breaker 11 → Motor Load A
Motor feeder BBus B → Breaker 12 → Motor Load B
Motor feeder CBus C → Breaker 13 → Motor Load C
Bus coupler 1Bus A → Bus Coupler 1 → Bus B
Bus coupler 2Bus B → Bus Coupler 2 → Bus C

Open the complete drawing at full size. The completed SLD download is the editable electrical model.

Three buses joined by two bus couplers, supplied by two grid branches and six generator branches, with three motor feeders and their relays.

2. Enter the parameter schedules

Open an equipment item with a double-click or Edit properties. The field names and units below match the study forms. Some inputs appear under the full Load flow, Short circuit or Earthing tabs rather than Essentials. Expand advanced sections when needed. A blank field is not zero: leave unspecified values blank and review any resulting warning.

Use these schedules for every repeated branch. The neutral-grounding-transformer symbol and its actual electrical grounding resistance are both included where used. Check both.

Grid 1Generator 1Generator 2Generator 3Generator 4Generator 5Generator 6Breaker 1Breaker 3Transformer 3Transformer 4Transformer 5Transformer 6Transformer 7Transformer 8Transformer 1Transformer 2Breaker 5Breaker 6Breaker 7Breaker 8Breaker 9Breaker 10Breaker 2Breaker 4Bus Coupler 1Bus Coupler 2Bus ABus BBus CBreaker 11Motor Load ABreaker 12Breaker 13Motor Load BMotor Load CGrid 2Relay 1Relay 3Relay 5Relay 6Relay 7Relay 8Relay 9Relay 10Relay 2Relay 4Relay 14Relay 15Relay 11Relay 12Relay 13
Grid 1 · Grid supply
Form / tabFieldValueUnit
DrawingSystem voltage132kV
DrawingIn serviceYes—
DrawingGrounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage132kV
Load flowVoltage setpoint1pu
Load flowVoltage angle0°
Short circuitMaximum short-circuit level5700MVA
Short circuitMaximum-case X/R20—
Short circuitMinimum short-circuit level1000MVA
Short circuitMinimum-case X/R7—
EarthingDefault grounding arrangementSolidly grounded—
EarthingX0 / X1 ratio1—
EarthingR0 / X0 ratio0.0714285714286—
Short circuitX2 / X1 ratio1—
Short circuitR2 / R1 ratio1—
EarthingSource neutral resistance0Ω
EarthingSource neutral reactance0Ω
Generator 1 · Generator
Form / tabFieldValueUnit
DrawingSystem voltage11kV
DrawingIn serviceNo—
DrawingGrounding symbolneutral-grounding-transformer—
DrawingGrounding transformer primary voltage (V)6350—
DrawingGrounding transformer secondary voltage (V)110—
DrawingGrounding transformer secondary resistance (Ω)0.4—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage11kV
GeneralRated apparent power29.4118MVA
GeneralRated active power25MW
GeneralRated power factor0.85—
Load flowGenerator control modeVoltage control · P + V (AVR)—
Load flowOperating active power0MW
Load flowReactive-power directionSupply reactive power (+Q)—
Load flowVoltage setpoint1.02pu
Load flowReference voltage angle0°
Load flowMinimum reactive power · Qmin-7.5MVAr
Load flowMaximum reactive power · Qmax15MVAr
Load flowReactive sharing at this busProportional to rated MVA—
Load flowReactive participation weight1—
Short circuitInclude generator fault contributionNo—
Short circuitSubtransient reactance Xd″15%
Short circuitSubtransient X/R45—
Short circuitMethod C fictitious resistance Rf1.05% on machine base
Short circuitNegative-sequence reactance X215%
Short circuitNegative-sequence X2/R220—
Short circuitPermanent generator-voltage deviation0.5%
EarthingDefault grounding arrangementResistance grounded—
EarthingStator connectionStar—
EarthingZero-sequence reactance X010%
EarthingZero-sequence X0/R08—
EarthingNeutral resistance1332.97520661Ω
EarthingNeutral reactance0Ω
Generator 2 · Generator
Form / tabFieldValueUnit
DrawingSystem voltage11kV
DrawingIn serviceYes—
DrawingGrounding symbolneutral-grounding-transformer—
DrawingGrounding transformer primary voltage (V)6350—
DrawingGrounding transformer secondary voltage (V)110—
DrawingGrounding transformer secondary resistance (Ω)0.4—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage11kV
GeneralRated apparent power42.5MVA
GeneralRated active power34.64MW
GeneralRated power factor0.85—
Load flowGenerator control modeVoltage control · P + V (AVR)—
Load flowOperating active power25.2650210108MW
Load flowReactive-power directionSupply reactive power (+Q)—
Load flowVoltage setpoint1.00125pu
Load flowReference voltage angle0°
Load flowMinimum reactive power · Qmin-12.75MVAr
Load flowMaximum reactive power · Qmax22.3882642248MVAr
Load flowReactive sharing at this busProportional to rated MVA—
Load flowReactive participation weight1—
Short circuitInclude generator fault contributionYes—
Short circuitSubtransient reactance Xd″15%
Short circuitSubtransient X/R50—
Short circuitMethod C fictitious resistance Rf1.05% on machine base
Short circuitNegative-sequence reactance X215%
Short circuitNegative-sequence X2/R220—
Short circuitPermanent generator-voltage deviation0.5%
EarthingDefault grounding arrangementResistance grounded—
EarthingStator connectionStar—
EarthingZero-sequence reactance X07.5%
EarthingZero-sequence X0/R09—
EarthingNeutral resistance1332.97520661Ω
EarthingNeutral reactance0Ω
Generator 3 · Generator
Form / tabFieldValueUnit
DrawingSystem voltage11kV
DrawingIn serviceYes—
DrawingGrounding symbolneutral-grounding-transformer—
DrawingGrounding transformer primary voltage (V)6350—
DrawingGrounding transformer secondary voltage (V)110—
DrawingGrounding transformer secondary resistance (Ω)0.4—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage11kV
GeneralRated apparent power20.9882MVA
GeneralRated active power17.84MW
GeneralRated power factor0.85—
Load flowGenerator control modeVoltage control · P + V (AVR)—
Load flowOperating active power13.0117775644MW
Load flowReactive-power directionSupply reactive power (+Q)—
Load flowVoltage setpoint1.00125pu
Load flowReference voltage angle0°
Load flowMinimum reactive power · Qmin-6.29646MVAr
Load flowMaximum reactive power · Qmax11.0562204048MVAr
Load flowReactive sharing at this busProportional to rated MVA—
Load flowReactive participation weight1—
Short circuitInclude generator fault contributionYes—
Short circuitSubtransient reactance Xd″14%
Short circuitSubtransient X/R40—
Short circuitMethod C fictitious resistance Rf0.98% on machine base
Short circuitNegative-sequence reactance X214%
Short circuitNegative-sequence X2/R218—
Short circuitPermanent generator-voltage deviation0.5%
EarthingDefault grounding arrangementResistance grounded—
EarthingStator connectionStar—
EarthingZero-sequence reactance X07%
EarthingZero-sequence X0/R09—
EarthingNeutral resistance1332.97520661Ω
EarthingNeutral reactance0Ω
Generator 4 · Generator
Form / tabFieldValueUnit
DrawingSystem voltage11kV
DrawingIn serviceYes—
DrawingGrounding symbolneutral-grounding-transformer—
DrawingGrounding transformer primary voltage (V)6351—
DrawingGrounding transformer secondary voltage (V)110—
DrawingGrounding transformer secondary resistance (Ω)0.4—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage11kV
GeneralRated apparent power42.7176MVA
GeneralRated active power36.31MW
GeneralRated power factor0.85—
Load flowGenerator control modeVoltage control · P + V (AVR)—
Load flowOperating active power26.4830517581MW
Load flowReactive-power directionSupply reactive power (+Q)—
Load flowVoltage setpoint1.00125pu
Load flowReference voltage angle0°
Load flowMinimum reactive power · Qmin-12.81528MVAr
Load flowMaximum reactive power · Qmax22.5028921376MVAr
Load flowReactive sharing at this busProportional to rated MVA—
Load flowReactive participation weight1—
Short circuitInclude generator fault contributionYes—
Short circuitSubtransient reactance Xd″13.5%
Short circuitSubtransient X/R35—
Short circuitMethod C fictitious resistance Rf0.945% on machine base
Short circuitNegative-sequence reactance X214.5%
Short circuitNegative-sequence X2/R225—
Short circuitPermanent generator-voltage deviation0%
EarthingDefault grounding arrangementResistance grounded—
EarthingStator connectionStar—
EarthingZero-sequence reactance X05.5%
EarthingZero-sequence X0/R04.5—
EarthingNeutral resistance1333.39507438Ω
EarthingNeutral reactance0Ω
Generator 5 · Generator
Form / tabFieldValueUnit
DrawingSystem voltage11kV
DrawingIn serviceNo—
DrawingGrounding symbolneutral-grounding-transformer—
DrawingGrounding transformer primary voltage (V)6351—
DrawingGrounding transformer secondary voltage (V)110—
DrawingGrounding transformer secondary resistance (Ω)0.4—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage11kV
GeneralRated apparent power42.7176MVA
GeneralRated active power36.31MW
GeneralRated power factor0.85—
Load flowGenerator control modeVoltage control · P + V (AVR)—
Load flowOperating active power0MW
Load flowReactive-power directionSupply reactive power (+Q)—
Load flowVoltage setpoint1.02pu
Load flowReference voltage angle0°
Load flowMinimum reactive power · Qmin-12.81528MVAr
Load flowMaximum reactive power · Qmax22.5028921376MVAr
Load flowReactive sharing at this busProportional to rated MVA—
Load flowReactive participation weight1—
Short circuitInclude generator fault contributionNo—
Short circuitSubtransient reactance Xd″13.5%
Short circuitSubtransient X/R35—
Short circuitMethod C fictitious resistance Rf0.945% on machine base
Short circuitNegative-sequence reactance X214.5%
Short circuitNegative-sequence X2/R225—
Short circuitPermanent generator-voltage deviation0%
EarthingDefault grounding arrangementResistance grounded—
EarthingStator connectionStar—
EarthingZero-sequence reactance X05.5%
EarthingZero-sequence X0/R04.5—
EarthingNeutral resistance1333.39507438Ω
EarthingNeutral reactance0Ω
Generator 6 · Generator
Form / tabFieldValueUnit
DrawingSystem voltage11kV
DrawingIn serviceYes—
DrawingGrounding symbolneutral-grounding-transformer—
DrawingGrounding transformer primary voltage (V)6351—
DrawingGrounding transformer secondary voltage (V)110—
DrawingGrounding transformer secondary resistance (Ω)0.4—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage11kV
GeneralRated apparent power41.1765MVA
GeneralRated active power35MW
GeneralRated power factor0.85—
Load flowGenerator control modeVoltage control · P + V (AVR)—
Load flowOperating active power25.5275905132MW
Load flowReactive-power directionSupply reactive power (+Q)—
Load flowVoltage setpoint1.00125pu
Load flowReference voltage angle0°
Load flowMinimum reactive power · Qmin-12.35295MVAr
Load flowMaximum reactive power · Qmax21.6910673377MVAr
Load flowReactive sharing at this busProportional to rated MVA—
Load flowReactive participation weight1—
Short circuitInclude generator fault contributionYes—
Short circuitSubtransient reactance Xd″13.5%
Short circuitSubtransient X/R35—
Short circuitMethod C fictitious resistance Rf0.945% on machine base
Short circuitNegative-sequence reactance X214.5%
Short circuitNegative-sequence X2/R225—
Short circuitPermanent generator-voltage deviation0%
EarthingDefault grounding arrangementResistance grounded—
EarthingStator connectionStar—
EarthingZero-sequence reactance X05.5%
EarthingZero-sequence X0/R04.5—
EarthingNeutral resistance1333.39507438Ω
EarthingNeutral reactance0Ω
Breaker 1 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage132kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage145kV
GeneralRated continuous current800A
Short circuitRated breaking current31.5kA rms
Short circuitRated making current80kA peak
Short circuitShort-time withstand current31.5kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Breaker 3 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage132kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage145kV
GeneralRated continuous current800A
Short circuitRated breaking current31.5kA rms
Short circuitRated making current80kA peak
Short circuitShort-time withstand current31.5kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Transformer 3 · Transformer
Form / tabFieldValueUnit
DrawingHigh-voltage terminal system voltage33kV
DrawingLow-voltage terminal system voltage11kV
DrawingIn serviceNo—
DrawingTransformer applicationgeneral—
DrawingHigh-voltage grounding symbolauto—
DrawingLow-voltage grounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated power35MVA
GeneralHV rated voltage34.5kV
GeneralLV rated voltage11kV
GeneralVector groupYNd1—
GeneralShort-circuit impedance12.5%
GeneralTransformer X/R20—
Load flowNo-load loss21kW
Load flowNo-load current0.3%
Load flowTap-changer sideHV winding—
Load flowNeutral tap position0—
Load flowMinimum tap position-8—
Load flowMaximum tap position8—
Load flowCurrent tap position0—
Load flowVoltage change per tap1.25%
Short circuitApply IEC transformer correction factor KTYes—
EarthingDefault grounding arrangementSolidly grounded—
EarthingHV winding groundingSolidly grounded—
EarthingLV winding groundingIsolated neutral—
EarthingZero-sequence connection modelAutomatic from vector group—
EarthingZero-sequence impedance12.5%
EarthingZero-sequence X/R20—
EarthingHV neutral resistance0Ω
EarthingHV neutral reactance0Ω
EarthingLV neutral resistance0Ω
EarthingLV neutral reactance0Ω
Transformer 4 · Transformer
Form / tabFieldValueUnit
DrawingHigh-voltage terminal system voltage33kV
DrawingLow-voltage terminal system voltage11kV
DrawingIn serviceYes—
DrawingTransformer applicationgeneral—
DrawingHigh-voltage grounding symbolauto—
DrawingLow-voltage grounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated power55MVA
GeneralHV rated voltage34.5kV
GeneralLV rated voltage11kV
GeneralVector groupYNd1—
GeneralShort-circuit impedance12.27%
GeneralTransformer X/R20—
Load flowNo-load loss33kW
Load flowNo-load current0.3%
Load flowTap-changer sideHV winding—
Load flowNeutral tap position0—
Load flowMinimum tap position-8—
Load flowMaximum tap position8—
Load flowCurrent tap position0—
Load flowVoltage change per tap1.25%
Short circuitApply IEC transformer correction factor KTYes—
EarthingDefault grounding arrangementSolidly grounded—
EarthingHV winding groundingSolidly grounded—
EarthingLV winding groundingIsolated neutral—
EarthingZero-sequence connection modelAutomatic from vector group—
EarthingZero-sequence impedance12.27%
EarthingZero-sequence X/R20—
EarthingHV neutral resistance0Ω
EarthingHV neutral reactance0Ω
EarthingLV neutral resistance0Ω
EarthingLV neutral reactance0Ω
Transformer 5 · Transformer
Form / tabFieldValueUnit
DrawingHigh-voltage terminal system voltage33kV
DrawingLow-voltage terminal system voltage11kV
DrawingIn serviceYes—
DrawingTransformer applicationgeneral—
DrawingHigh-voltage grounding symbolauto—
DrawingLow-voltage grounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated power25MVA
GeneralHV rated voltage34.5kV
GeneralLV rated voltage11kV
GeneralVector groupYNd1—
GeneralShort-circuit impedance9.95%
GeneralTransformer X/R20—
Load flowNo-load loss15kW
Load flowNo-load current0.3%
Load flowTap-changer sideHV winding—
Load flowNeutral tap position0—
Load flowMinimum tap position-8—
Load flowMaximum tap position8—
Load flowCurrent tap position0—
Load flowVoltage change per tap1.25%
Short circuitApply IEC transformer correction factor KTYes—
EarthingDefault grounding arrangementSolidly grounded—
EarthingHV winding groundingSolidly grounded—
EarthingLV winding groundingIsolated neutral—
EarthingZero-sequence connection modelAutomatic from vector group—
EarthingZero-sequence impedance9.95%
EarthingZero-sequence X/R20—
EarthingHV neutral resistance0Ω
EarthingHV neutral reactance0Ω
EarthingLV neutral resistance0Ω
EarthingLV neutral reactance0Ω
Transformer 6 · Transformer
Form / tabFieldValueUnit
DrawingHigh-voltage terminal system voltage33kV
DrawingLow-voltage terminal system voltage11kV
DrawingIn serviceYes—
DrawingTransformer applicationgeneral—
DrawingHigh-voltage grounding symbolauto—
DrawingLow-voltage grounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated power55MVA
GeneralHV rated voltage34.5kV
GeneralLV rated voltage11kV
GeneralVector groupYNd1—
GeneralShort-circuit impedance12.17%
GeneralTransformer X/R20—
Load flowNo-load loss33kW
Load flowNo-load current0.3%
Load flowTap-changer sideHV winding—
Load flowNeutral tap position0—
Load flowMinimum tap position-8—
Load flowMaximum tap position8—
Load flowCurrent tap position0—
Load flowVoltage change per tap1.25%
Short circuitApply IEC transformer correction factor KTYes—
EarthingDefault grounding arrangementSolidly grounded—
EarthingHV winding groundingSolidly grounded—
EarthingLV winding groundingIsolated neutral—
EarthingZero-sequence connection modelAutomatic from vector group—
EarthingZero-sequence impedance12.17%
EarthingZero-sequence X/R20—
EarthingHV neutral resistance0Ω
EarthingHV neutral reactance0Ω
EarthingLV neutral resistance0Ω
EarthingLV neutral reactance0Ω
Transformer 7 · Transformer
Form / tabFieldValueUnit
DrawingHigh-voltage terminal system voltage33kV
DrawingLow-voltage terminal system voltage11kV
DrawingIn serviceNo—
DrawingTransformer applicationgeneral—
DrawingHigh-voltage grounding symbolauto—
DrawingLow-voltage grounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated power55MVA
GeneralHV rated voltage34.5kV
GeneralLV rated voltage11kV
GeneralVector groupYNd1—
GeneralShort-circuit impedance12.06%
GeneralTransformer X/R20—
Load flowNo-load loss33kW
Load flowNo-load current0.3%
Load flowTap-changer sideHV winding—
Load flowNeutral tap position0—
Load flowMinimum tap position-8—
Load flowMaximum tap position8—
Load flowCurrent tap position0—
Load flowVoltage change per tap1.25%
Short circuitApply IEC transformer correction factor KTYes—
EarthingDefault grounding arrangementSolidly grounded—
EarthingHV winding groundingSolidly grounded—
EarthingLV winding groundingIsolated neutral—
EarthingZero-sequence connection modelAutomatic from vector group—
EarthingZero-sequence impedance12.06%
EarthingZero-sequence X/R20—
EarthingHV neutral resistance0Ω
EarthingHV neutral reactance0Ω
EarthingLV neutral resistance0Ω
EarthingLV neutral reactance0Ω
Transformer 8 · Transformer
Form / tabFieldValueUnit
DrawingHigh-voltage terminal system voltage33kV
DrawingLow-voltage terminal system voltage11kV
DrawingIn serviceYes—
DrawingTransformer applicationgeneral—
DrawingHigh-voltage grounding symbolauto—
DrawingLow-voltage grounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated power55MVA
GeneralHV rated voltage34.5kV
GeneralLV rated voltage11kV
GeneralVector groupYNd1—
GeneralShort-circuit impedance15.43%
GeneralTransformer X/R20—
Load flowNo-load loss33kW
Load flowNo-load current0.3%
Load flowTap-changer sideHV winding—
Load flowNeutral tap position0—
Load flowMinimum tap position-8—
Load flowMaximum tap position8—
Load flowCurrent tap position0—
Load flowVoltage change per tap1.25%
Short circuitApply IEC transformer correction factor KTYes—
EarthingDefault grounding arrangementSolidly grounded—
EarthingHV winding groundingSolidly grounded—
EarthingLV winding groundingIsolated neutral—
EarthingZero-sequence connection modelAutomatic from vector group—
EarthingZero-sequence impedance15.43%
EarthingZero-sequence X/R20—
EarthingHV neutral resistance0Ω
EarthingHV neutral reactance0Ω
EarthingLV neutral resistance0Ω
EarthingLV neutral reactance0Ω
Transformer 1 · Transformer
Form / tabFieldValueUnit
DrawingHigh-voltage terminal system voltage132kV
DrawingLow-voltage terminal system voltage33kV
DrawingIn serviceYes—
DrawingTransformer applicationgeneral—
DrawingHigh-voltage grounding symbolauto—
DrawingLow-voltage grounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated power50MVA
GeneralHV rated voltage132kV
GeneralLV rated voltage34.5kV
GeneralVector groupYNyn0—
GeneralShort-circuit impedance11.225%
GeneralTransformer X/R20—
Load flowNo-load loss30kW
Load flowNo-load current0.3%
Load flowTap-changer sideHV winding—
Load flowNeutral tap position0—
Load flowMinimum tap position-8—
Load flowMaximum tap position8—
Load flowCurrent tap position3—
Load flowVoltage change per tap1.25%
Short circuitApply IEC transformer correction factor KTYes—
EarthingDefault grounding arrangementSolidly grounded—
EarthingHV winding groundingSolidly grounded—
EarthingLV winding groundingSolidly grounded—
EarthingZero-sequence connection modelAutomatic from vector group—
EarthingZero-sequence impedance11.225%
EarthingZero-sequence X/R20—
EarthingHV neutral resistance0Ω
EarthingHV neutral reactance0Ω
EarthingLV neutral resistance0Ω
EarthingLV neutral reactance0Ω
Transformer 2 · Transformer
Form / tabFieldValueUnit
DrawingHigh-voltage terminal system voltage132kV
DrawingLow-voltage terminal system voltage33kV
DrawingIn serviceYes—
DrawingTransformer applicationgeneral—
DrawingHigh-voltage grounding symbolauto—
DrawingLow-voltage grounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated power50MVA
GeneralHV rated voltage132kV
GeneralLV rated voltage34.5kV
GeneralVector groupYNyn0—
GeneralShort-circuit impedance10.889%
GeneralTransformer X/R20—
Load flowNo-load loss30kW
Load flowNo-load current0.3%
Load flowTap-changer sideHV winding—
Load flowNeutral tap position0—
Load flowMinimum tap position-8—
Load flowMaximum tap position8—
Load flowCurrent tap position3—
Load flowVoltage change per tap1.25%
Short circuitApply IEC transformer correction factor KTYes—
EarthingDefault grounding arrangementSolidly grounded—
EarthingHV winding groundingSolidly grounded—
EarthingLV winding groundingSolidly grounded—
EarthingZero-sequence connection modelAutomatic from vector group—
EarthingZero-sequence impedance10.889%
EarthingZero-sequence X/R20—
EarthingHV neutral resistance0Ω
EarthingHV neutral reactance0Ω
EarthingLV neutral resistance0Ω
EarthingLV neutral reactance0Ω
Breaker 5 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateopen—
DrawingOperating stateopen—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current1250A
Short circuitRated breaking current26.3kA rms
Short circuitRated making current65.75kA peak
Short circuitShort-time withstand current26.3kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Breaker 6 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current1250A
Short circuitRated breaking current26.3kA rms
Short circuitRated making current65.75kA peak
Short circuitShort-time withstand current26.3kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Breaker 7 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current1250A
Short circuitRated breaking current26.3kA rms
Short circuitRated making current65.75kA peak
Short circuitShort-time withstand current26.3kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Breaker 8 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current1250A
Short circuitRated breaking current26.3kA rms
Short circuitRated making current65.75kA peak
Short circuitShort-time withstand current26.3kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Breaker 9 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateopen—
DrawingOperating stateopen—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current1250A
Short circuitRated breaking current26.3kA rms
Short circuitRated making current65.75kA peak
Short circuitShort-time withstand current26.3kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Breaker 10 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current2000A
Short circuitRated breaking current31.5kA rms
Short circuitRated making current78.75kA peak
Short circuitShort-time withstand current31.5kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Breaker 2 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current1250A
Short circuitRated breaking current40kA rms
Short circuitRated making current100kA peak
Short circuitShort-time withstand current40kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Breaker 4 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current1250A
Short circuitRated breaking current40kA rms
Short circuitRated making current100kA peak
Short circuitShort-time withstand current40kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Bus Coupler 1 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current2000A
Short circuitRated breaking current26.3kA rms
Short circuitRated making current65.75kA peak
Short circuitShort-time withstand current26.3kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Bus Coupler 2 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current2000A
Short circuitRated breaking current26.3kA rms
Short circuitRated making current65.75kA peak
Short circuitShort-time withstand current26.3kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time70ms
Bus A · Bus
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingBus drawing length (px)900—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage33kV
GeneralRated continuous current2000A
Short circuitShort-time withstand current (reference)40kA rms
Short circuitWithstand duration (reference)3s
Bus B · Bus
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingBus drawing length (px)900—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage33kV
GeneralRated continuous current2000A
Short circuitShort-time withstand current (reference)26.3kA rms
Short circuitWithstand duration (reference)3s
Bus C · Bus
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingBus drawing length (px)900—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage33kV
GeneralRated continuous current2000A
Short circuitShort-time withstand current (reference)26.3kA rms
Short circuitWithstand duration (reference)3s
Breaker 11 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current1250A
Short circuitRated breaking current31.5kA rms
Short circuitRated making current80kA peak
Short circuitShort-time withstand current31.5kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time80ms
Motor Load A · Motor load
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingGrounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage33kV
GeneralRated mechanical output30000kW
GeneralPole pairs2—
GeneralRated efficiency95%
GeneralRated power factor0.88—
GeneralStarting methodDirect-on-line—
Load flowOperating mechanical loading100%
Load flowOperating power factor0.88—
Load flowOperating efficiency95%
Load flowDemand factor1—
Short circuitInclude motor fault contributionYes—
Short circuitLocked-rotor current multiple6×In
Short circuitFault-current X/R10—
Short circuitContribution duration200ms
EarthingDefault grounding arrangementIsolated neutral—
EarthingStator connectionDelta—
Short circuitX2 / X1 ratio1—
Short circuitR2 / R1 ratio1—
Breaker 12 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current1250A
Short circuitRated breaking current31.5kA rms
Short circuitRated making current80kA peak
Short circuitShort-time withstand current31.5kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time80ms
Breaker 13 · Breaker / bus coupler
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingNormal stateclosed—
DrawingOperating stateclosed—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage36kV
GeneralRated continuous current1250A
Short circuitRated breaking current31.5kA rms
Short circuitRated making current80kA peak
Short circuitShort-time withstand current31.5kA rms
Short circuitShort-time withstand duration3s
Short circuitTotal clearing time80ms
Motor Load B · Motor load
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingGrounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage33kV
GeneralRated mechanical output30000kW
GeneralPole pairs2—
GeneralRated efficiency95%
GeneralRated power factor0.88—
GeneralStarting methodDirect-on-line—
Load flowOperating mechanical loading100%
Load flowOperating power factor0.88—
Load flowOperating efficiency95%
Load flowDemand factor1—
Short circuitInclude motor fault contributionYes—
Short circuitLocked-rotor current multiple6×In
Short circuitFault-current X/R10—
Short circuitContribution duration200ms
EarthingDefault grounding arrangementIsolated neutral—
EarthingStator connectionDelta—
Short circuitX2 / X1 ratio1—
Short circuitR2 / R1 ratio1—
Motor Load C · Motor load
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingGrounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage33kV
GeneralRated mechanical output30000kW
GeneralPole pairs2—
GeneralRated efficiency95%
GeneralRated power factor0.88—
GeneralStarting methodDirect-on-line—
Load flowOperating mechanical loading100%
Load flowOperating power factor0.88—
Load flowOperating efficiency95%
Load flowDemand factor1—
Short circuitInclude motor fault contributionYes—
Short circuitLocked-rotor current multiple6×In
Short circuitFault-current X/R10—
Short circuitContribution duration200ms
EarthingDefault grounding arrangementIsolated neutral—
EarthingStator connectionDelta—
Short circuitX2 / X1 ratio1—
Short circuitR2 / R1 ratio1—
Grid 2 · Grid supply
Form / tabFieldValueUnit
DrawingSystem voltage132kV
DrawingIn serviceYes—
DrawingGrounding symbolauto—
GeneralData sourceEngineering assumption—
GeneralRated / nominal voltage132kV
Load flowVoltage setpoint1pu
Load flowVoltage angle0°
Short circuitMaximum short-circuit level5700MVA
Short circuitMaximum-case X/R20—
Short circuitMinimum short-circuit level1000MVA
Short circuitMinimum-case X/R7—
EarthingDefault grounding arrangementSolidly grounded—
EarthingX0 / X1 ratio1—
EarthingR0 / X0 ratio0.0714285714286—
Short circuitX2 / X1 ratio1—
Short circuitR2 / R1 ratio1—
EarthingSource neutral resistance0Ω
EarthingSource neutral reactance0Ω
Relay 1 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage132kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 1
Measured terminalTerminal 1
Phase CT ratio300 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio300 / 1 A
Trip breakerBreaker 1
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes0.916666666667275IEC standard inverse0.950
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.2575IEC standard inverse0.950
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 3 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage132kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 3
Measured terminalTerminal 1
Phase CT ratio300 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio300 / 1 A
Trip breakerBreaker 3
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes0.916666666667275IEC standard inverse0.950
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.2575IEC standard inverse0.950
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 5 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 5
Measured terminalTerminal 1
Phase CT ratio800 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio800 / 1 A
Trip breakerBreaker 5
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes0.85680IEC standard inverse0.40
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.1875150IEC standard inverse0.40
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 6 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 6
Measured terminalTerminal 1
Phase CT ratio1000 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio1000 / 1 A
Trip breakerBreaker 6
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes11000IEC standard inverse0.750
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.15150IEC standard inverse0.750
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 7 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 7
Measured terminalTerminal 1
Phase CT ratio600 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio600 / 1 A
Trip breakerBreaker 7
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes0.833333333333500IEC standard inverse0.650
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.166666666667100IEC standard inverse0.650
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 8 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 8
Measured terminalTerminal 1
Phase CT ratio1000 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio1000 / 1 A
Trip breakerBreaker 8
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes11000IEC standard inverse0.70
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.15150IEC standard inverse0.70
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 9 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 9
Measured terminalTerminal 1
Phase CT ratio1000 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio1000 / 1 A
Trip breakerBreaker 9
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes11000IEC standard inverse0.40
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.15150IEC standard inverse0.40
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 10 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 10
Measured terminalTerminal 1
Phase CT ratio1000 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio1000 / 1 A
Trip breakerBreaker 10
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes11000IEC standard inverse0.70
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.15150IEC standard inverse0.70
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 2 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 2
Measured terminalTerminal 1
Phase CT ratio1200 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio1200 / 1 A
Trip breakerBreaker 2
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes0.9166666666671100IEC standard inverse0.70
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.125150IEC standard inverse0.70
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 4 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 4
Measured terminalTerminal 1
Phase CT ratio1200 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio1200 / 1 A
Trip breakerBreaker 4
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes0.9166666666671100IEC standard inverse0.70
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.125150IEC standard inverse0.70
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 14 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBus Coupler 1
Measured terminalTerminal 1
Phase CT ratio2000 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio2000 / 1 A
Trip breakerBus Coupler 1
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes0.61200IEC standard inverse0.50
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.05100IEC standard inverse0.50
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 15 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBus Coupler 2
Measured terminalTerminal 1
Phase CT ratio2000 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio2000 / 1 A
Trip breakerBus Coupler 2
Maximum breaker-only time (s)0.07
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes0.61200IEC standard inverse0.50
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.05100IEC standard inverse0.50
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 11 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 11
Measured terminalTerminal 1
Phase CT ratio800 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio800 / 1 A
Trip breakerBreaker 11
Maximum breaker-only time (s)0.08
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes1800IEC standard inverse0.10
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.07560IEC standard inverse0.10
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 12 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 12
Measured terminalTerminal 1
Phase CT ratio800 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio800 / 1 A
Trip breakerBreaker 12
Maximum breaker-only time (s)0.08
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes1800IEC standard inverse0.10
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.07560IEC standard inverse0.10
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Relay 13 · Relay
Form / tabFieldValueUnit
DrawingSystem voltage33kV
DrawingIn serviceYes—
DrawingFunctions51 / 51N (provisional)—
DrawingManufacturerUnspecified—
DrawingRelay modelGeneric IEC SI—
GeneralData sourceEngineering assumption—
Relay assignmentValue
Measured equipmentBreaker 13
Measured terminalTerminal 1
Phase CT ratio800 / 1 A
Earth inputCalculated residual from the phase CT set
Earth CT ratio800 / 1 A
Trip breakerBreaker 13
Maximum breaker-only time (s)0.08
Additional trip delay (s)0
Current error (%)5
Timing error (%)5
Additional timing error (s)0.02
Grading margin (s)0.3
Voltage inputNot assigned; this exercise uses overcurrent elements
StageEnabledSecondary pickup (A)Primary pickup (A)CurveTime multiplierDefinite delay (s)
I>Yes1800IEC standard inverse0.10
I>>NoNot enteredNot enteredDefinite time0.10
I>>>NoNot enteredNot enteredDefinite time0.10
Ie>Yes0.07560IEC standard inverse0.10
Ie>>NoNot enteredNot enteredDefinite time0.10
Ie>>>NoNot enteredNot enteredDefinite time0.10
Overhead Line 1 · Overhead line
Form / tabFieldValueUnit
DrawingIn serviceYes—
GeneralData sourceEngineering assumption—
GeneralPhysical route length1.7km
GeneralParallel circuits / runs1—
GeneralR1 reference temperature20°C
GeneralPositive-sequence resistance R10.139026Ω/km
GeneralResistance temperature coefficient α at R1 reference temperature0.004031/°C
GeneralLoad-flow conductor temperature75°C
Short circuitMaximum-fault conductor temperature20°C
GeneralPositive-sequence reactance X10.39Ω/km
Load flowPositive-sequence capacitance C19.4nF/km
GeneralContinuous current rating377A
GeneralDerating factor1—
Short circuitFault end temperature200°C
EarthingZero-sequence resistance R00.45Ω/km
EarthingZero-sequence reactance X01.2Ω/km
EarthingZero-sequence capacitance C06nF/km
Overhead Line 2 · Overhead line
Form / tabFieldValueUnit
DrawingIn serviceYes—
GeneralData sourceEngineering assumption—
GeneralPhysical route length1.7km
GeneralParallel circuits / runs1—
GeneralR1 reference temperature20°C
GeneralPositive-sequence resistance R10.139026Ω/km
GeneralResistance temperature coefficient α at R1 reference temperature0.004031/°C
GeneralLoad-flow conductor temperature75°C
Short circuitMaximum-fault conductor temperature20°C
GeneralPositive-sequence reactance X10.39Ω/km
Load flowPositive-sequence capacitance C19.4nF/km
GeneralContinuous current rating377A
GeneralDerating factor1—
Short circuitFault end temperature200°C
EarthingZero-sequence resistance R00.45Ω/km
EarthingZero-sequence reactance X01.2Ω/km
EarthingZero-sequence capacitance C06nF/km

3. Check every terminal connection

Use these endpoints when repeating the drawing. Bus tap identifiers are intentionally shown as “Bus tap”; place each tap above or below the corresponding branch so its conductor stays vertical. Horizontal couplers connect facing bus ends.

TypeFromTo
ConductorTransformer 7 · High-voltage terminalBreaker 9 · Terminal 1
ConductorBreaker 5 · Terminal 2Bus A · Bus tap
ConductorGenerator 4 · TerminalTransformer 6 · Low-voltage terminal
ConductorGenerator 1 · TerminalTransformer 3 · Low-voltage terminal
ConductorTransformer 8 · High-voltage terminalBreaker 10 · Terminal 1
ConductorTransformer 6 · High-voltage terminalBreaker 8 · Terminal 1
ConductorTransformer 1 · Low-voltage terminalBreaker 2 · Terminal 1
ConductorBreaker 9 · Terminal 2Bus C · Bus tap
ConductorBreaker 7 · Terminal 2Bus B · Bus tap
ConductorBreaker 2 · Terminal 2Bus A · Bus tap
ConductorGenerator 3 · TerminalTransformer 5 · Low-voltage terminal
ConductorTransformer 5 · High-voltage terminalBreaker 7 · Terminal 1
ConductorGenerator 5 · TerminalTransformer 7 · Low-voltage terminal
ConductorBreaker 1 · Terminal 2Transformer 1 · High-voltage terminal
ConductorBreaker 4 · Terminal 2Bus C · Bus tap
ConductorBreaker 3 · Terminal 2Transformer 2 · High-voltage terminal
Overhead lineGrid 1 · TerminalBreaker 1 · Terminal 1
ConductorGenerator 2 · TerminalTransformer 4 · Low-voltage terminal
ConductorBreaker 10 · Terminal 2Bus C · Bus tap
ConductorTransformer 3 · High-voltage terminalBreaker 5 · Terminal 1
ConductorTransformer 4 · High-voltage terminalBreaker 6 · Terminal 1
ConductorBreaker 8 · Terminal 2Bus B · Bus tap
ConductorTransformer 2 · Low-voltage terminalBreaker 4 · Terminal 1
ConductorGenerator 6 · TerminalTransformer 8 · Low-voltage terminal
ConductorBreaker 11 · Terminal 2Motor Load A · Terminal
ConductorBreaker 11 · Terminal 1Bus A · Bus tap
ConductorBreaker 12 · Terminal 1Bus B · Bus tap
ConductorBreaker 13 · Terminal 1Bus C · Bus tap
ConductorBreaker 13 · Terminal 2Motor Load C · Terminal
ConductorBreaker 12 · Terminal 2Motor Load B · Terminal
Overhead lineGrid 2 · TerminalBreaker 3 · Terminal 1
ConductorBus A · rightBus Coupler 1 · Terminal 2
ConductorBus Coupler 1 · Terminal 1Bus B · left
ConductorBus B · rightBus Coupler 2 · Terminal 2
ConductorBus Coupler 2 · Terminal 1Bus C · left
ConductorBreaker 6 · Terminal 2Bus A · Bus tap
Relay trip linkRelay 1 · Trip outputBreaker 1 · Trip input
Relay trip linkRelay 3 · Trip outputBreaker 3 · Trip input
Relay trip linkRelay 5 · Trip outputBreaker 5 · Trip input
Relay trip linkRelay 6 · Trip outputBreaker 6 · Trip input
Relay trip linkRelay 7 · Trip outputBreaker 7 · Trip input
Relay trip linkRelay 8 · Trip outputBreaker 8 · Trip input
Relay trip linkRelay 9 · Trip outputBreaker 9 · Trip input
Relay trip linkRelay 10 · Trip outputBreaker 10 · Trip input
Relay trip linkRelay 2 · Trip outputBreaker 2 · Trip input
Relay trip linkRelay 4 · Trip outputBreaker 4 · Trip input
Relay trip linkRelay 14 · Trip outputBus Coupler 1 · Trip input
Relay trip linkRelay 15 · Trip outputBus Coupler 2 · Trip input
Relay trip linkRelay 11 · Trip outputBreaker 11 · Trip input
Relay trip linkRelay 12 · Trip outputBreaker 12 · Trip input
Relay trip linkRelay 13 · Trip outputBreaker 13 · Trip input

4. Run, interpret and compare the studies

Operating cases and load flow

  1. Use the normal operating case with 100% load and generation. Generator 1 and Generator 5, their transformers and breakers are out of service/open; the other four generator branches and both couplers are in service.
  2. Run Load flow and check the validation messages before reading the result cards. Inspect bus voltage, loading, real/reactive power, losses and source contributions.
  3. Create a second case called Reduced load. Set load scaling to 80%, keep generation at 100%, run it, then compare both cases. A change of sign in grid power indicates import versus export.
  4. Return to the normal case before the fault and coordination exercises. Changing a model or case requires a new calculation.
CheckNormal caseReduced-load case
Bus voltages1.000–1.005 puReview the new solved values
Highest load factor100%80%
Series real lossesAbout 0.385 MWAbout 0.370 MW
Grid 1 real power+2.463 MW−6.876 MW
Grid 2 real power+2.537 MW−7.086 MW
Net grid interchange5.000 MW import13.962 MW export

Short circuit and equipment duty

Select the normal operating case. Use a bolted fault (0 Ω resistance and reactance), 1 s fault duration, 100 ms minimum breaking time, established sources and automatic peak-factor method. Include generators and motors for the maximum case. Compare maximum three-phase, minimum three-phase and maximum phase-to-earth cases; inspect the study scope and contributions in each result.

Check at a 33 kV busRecorded result / interpretation
Maximum three-phase initial current38.073 kA RMS
Maximum three-phase peak current97.543 kA peak
Breaking current at the stated 100 ms32.232 kA RMS
Thermal equivalent at the stated 1 s38.975 kA RMS
Minimum three-phase initial current20.105 kA RMS; motor contribution is excluded automatically for this minimum case
Maximum earth-fault initial current39.106 kA RMS
26.3 kA bus ratingFails the shown comparison; do not hide the finding
Breaker 11 through-current for a bus fault4.144 kA motor backfeed in this example; local equipment current differs from total bus fault current
Time-dependent breaker dutiesSome making, breaking and thermal assessments are indeterminate because the model lacks required capabilities/data. A rating entry alone does not resolve the limitation.

Relay coordination

  1. Set a maximum three-phase fault at the Motor Load A terminal. Select Relay 11 as the primary and Relay 14 as the backup in the coordination wizard.
  2. Check CT assignments, local relay currents, curve families and the 0.30 s grading requirement. Compare maximum and minimum fault cases. The two relays do not necessarily measure the same current.
  3. Read the TCC and the worst-case timing table together. A pass for one declared pair is not proof of coordination across the entire network.
Pair checkMaximum faultMinimum fault
Primary latest clearing0.292 s0.324 s
Backup earliest trip1.046 s1.348 s
Available grading margin0.754 s1.024 s
Required grading margin0.300 s0.300 s

Healthy and failed-breaker sequences

Run the healthy sequence and record which breaker clears the fault. Then select Breaker 11 as stuck closed and run again. Read the full event list: compare the fault-clear time, the failed device state and every additional breaker opened. This is a stuck-breaker sequence study; it is not a simulation or commissioning test of a dedicated breaker-failure protection scheme.

SequenceExpected evidence
HealthyRelay 11 trips at about 0.180 s; Breaker 11 opens at 0.260 s and clears the fault.
Breaker 11 stuck closedBreaker 11 remains closed. Breakers 12 and 13 open at about 0.499 s, Bus Coupler 1 at 1.323 s, Breaker 2 at 2.611 s, and Breaker 6 at 4.710 s. Five other breakers open before clearance.
InterpretationLate clearance and loss of healthy feeders are findings to investigate, even when the simulator reports that the fault eventually cleared.

Try a setting proposal on a copy

Keep Relay 11 fixed. For the exercise only, assume Relay 14 maximum normal current is 1000 A; use 25% pickup headroom, minimum fault/pickup ratio 1.5, pickup step 0.01 A secondary, time-multiplier step 0.01, margin 0.30 s and maximum clearing time 3 s. The recorded candidate is 0.66 A secondary (1320 A primary) and time multiplier 0.28, with about 0.305 s maximum-case and 0.455 s minimum-case margin. Review, apply to a training copy, rerun and save it separately. Undo or reload the original before reproducing the original report results. The assumed 1000 A is not a verified operating limit.

5. Prepare the report and download your evidence

  1. Set the drawing title, project number, revision and preparation details. Populate checker and approver fields only with real review information; the tutorial leaves them unapproved.
  2. Open the report for the active study. Review the study matrix, input provenance, unresolved findings and completeness. Calculate every case needed for your report, rather than assuming the currently displayed result covers all cases.
  3. Download the audit CSV and preliminary PDF. Keep separate load-flow and short-circuit reports; each has its own scope and assumptions.
  4. Download the protection review and coordination results from their respective study panels. Preserve the actual settings and event sequence alongside the report.
  5. Open every downloaded file. Check title, revision, case names, current snapshot, units, findings and the input/output schedules. A successful download does not mean the design is approved.
  6. Save the editable SLD project JSON. Use Export SVG for a vector image, or Export PDF with A2 landscape and fit-to-page for this wide drawing. Use tiled pages when a single sheet makes text too small.

Keep the different file types straight

FileUse
SLD project JSONEditable network, equipment data, cases and settings; reopen it in SLD Studio.
Study report PDFReadable calculation scope, findings, inputs and outputs.
Audit CSVDetailed schedules for checking and further analysis.
Protection review HTML / coordination CSVRelay inputs, pair checks and sequence evidence.
Drawing SVG / vector PDFA picture of the drawing; this does not replace the editable electrical project.

6. Prove you can repeat the workflow

If any task is unclear, return to its chapter and repeat the action in your own project. Use verified equipment and utility data for real studies, and have the design and protection settings reviewed before use.

SLD Studio course · version 2.10.5 · 16 chapters · captions only · no narration.